Hey guys, Im in the process of moving to a new place. The wall where I want to mount TV doesnt have any power socket, but there is indoor A/C unit just next to it. Can I just connect a power strip cable to A/C unit terminals and use it as a socket for my LCD TV? Is there any risk Im not aware of?

I live in EU and have 220V AC mains. AC is ~1kW indoor unit and also ~1kW outdoor unit. TV is just regular 43" LCD.

I have a general knowledge about electricity (high school), but have no experience with A/C units.

Cheers

  • JackFrostNCola@lemmy.world
    link
    fedilink
    English
    arrow-up
    1
    ·
    edit-2
    1 year ago

    Assuming this is a VRF/DX split system you can often hang a small Outside Air Fan off the indoor unit power supply with no problems but anything over an Amp or so you are starting to risk overloading the PCBs in the Condensor unit as they dont have the same current carrying capacity as the cables typically used.

    Also not sure about the regulations where you live but you also need to comsider if the GPO for the TV would still be RCD/TCBo protected.

    Overall its a bad idea to be putting any non-HVAC related equipment on a circuit designated for an AC unit, this will be confusing and dangerous in regards to power isolation for an electrician doing work in future.

    • rambos@lemm.eeOP
      link
      fedilink
      English
      arrow-up
      1
      ·
      1 year ago

      Thank you. 1A is not what I need, but it feels bad after reading this. 1A is only ~220W which seems like dangerously low